Inspection
Inspection Details
Equipment ID
17738
17738
Inspection Date
7/24/2018
7/24/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
15ab0cae-f84a-421e-88d7-a45a44f77e8f
15ab0cae-f84a-421e-88d7-a45a44f77e8f
Location
Forest Park Station
250 DE BALIVIERE AVE, SAINT LOUIS, MO
250 DE BALIVIERE AVE, SAINT LOUIS, MO
Owner
Metro Accounts Payable
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Billing
Attn: Metro Accounts Payable
PO BOX 1349, SAINT LOUIS, MO 63188-1349
PO BOX 1349, SAINT LOUIS, MO 63188-1349
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 11/4/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | Stop switch not working. | 7/23/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post State certificate in machine room | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance conttrol program on site posted on controller | 11/4/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need fire service log posted in machine room to be be tested monthly | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Water damage on electric disconnects in machine room | 11/4/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | Yes | OSV test performed, elevator would not level at top landing and kept hitting stop ring. Red tagged elevator. | 7/28/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 7/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Severe water damage. | 7/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean oil from elevator pit. | 11/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | No | Cylinder head on hydraulic jack has leaking packing seal, need to replace seal. Re-inspection required | 10/26/2023 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | No | No | Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required | 1/17/2025 |