Inspection
Inspection Details
Equipment ID
10664
10664
Inspection Date
8/6/2018
8/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Scott Tiemann
Scott Tiemann
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
9c0e51a6-767b-481a-a79c-d86846386c9e
9c0e51a6-767b-481a-a79c-d86846386c9e
Location
Monastery of the Visitation Academy
3020 N BALLAS RD, SAINT LOUIS, MO
3020 N BALLAS RD, SAINT LOUIS, MO
Owner
Monastery of the Visitation Academy
3020 N BALLAS RD, SAINT LOUIS, MO 63131-2316
3020 N BALLAS RD, SAINT LOUIS, MO 63131-2316
Billing
Attn: Monastery of the Visitation Academy
3020 N BALLAS RD, SAINT LOUIS, MO 63131-2316
3020 N BALLAS RD, SAINT LOUIS, MO 63131-2316
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Cab phone line inoperative. | 10/15/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 2/2/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | After the call acknowledgement signals are sent, the two way voice communications shall be available between the car & authorized personnel. Re-inspection required | 12/13/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Door pressure too high, over 30 lbs, needs repair. Re-inspection required | 11/30/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 12/3/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. | 12/3/2024 |
| A17.1-1996 : Elevators | 1.9 - Power closing of doors or gates | 112.3 | Yes | No | The bottom car door reopening device (electric eye) was not working on the day of inspection. Repair or replace the reopening device for passenger safety. | 12/3/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service Phase I is not working. Re-inspection required | 11/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service Phase II is not working. Re-inspection required |