Inspection
Inspection Details
Equipment ID
20813
20813
Inspection Date
8/4/2021
8/4/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
28a9f698-3646-4812-9d24-e001660550eb
28a9f698-3646-4812-9d24-e001660550eb
Location
South City Academy
2900 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 881-0363
2900 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 881-0363
Owner
South City Preparatory School
2900 S GRAND BLVD, SAINT LOUIS, MO 63118-1005
2900 S GRAND BLVD, SAINT LOUIS, MO 63118-1005
Billing
Attn: South City Preparatory School
2900 S GRAND BLVD, SAINT LOUIS, MO 63118-1005
2900 S GRAND BLVD, SAINT LOUIS, MO 63118-1005
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.2 | Yes | No | The emergency phone shall be operational. | 8/4/2023 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.2 | Yes | No | The emergency phone shall be operational (2nd Notice). | 10/12/2023 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.2 | Yes | No | Phone must be able to reach live person by pushing the call button. Note: Once the call button is pressed, the call is picked up by an automated operator asking for the person to press 1 or 2, which is not an option from the lift. | 11/7/2023 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.2 | Yes | No | 2-way communication device shall work and be answered 24/7. Phone calls out, goes straight to voicemail. | 8/6/2026 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.6.3 Auxiliary Lighting (Re-Inspection) | Yes | No | Emergency lighting shall work. Test button is broken, location of lighting breaker is unknown. | 8/6/2026 |
| Missouri Minimum : Platform Lifts | (U) - Existing Vertical and Inclined Platform Lifts | (U)1 (Re-Inspect) | Yes | No | Pit stop switch and housing are damaged. Repair and re-test. | 8/6/2026 |
| Missouri Minimum : Platform Lifts | (U) - Existing Vertical and Inclined Platform Lifts | (U)1 | No | No | Electrical box in pit area is pulled from wall and damaged. Wiring is exposed. Repair as needed. | 8/6/2026 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.2 | Yes | No | Emergency two-way communication device is not funcitionin and shall be prepaired. | |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.6.3 Auxiliary Lighting (Re-Inspection) | Yes | No | Emergency lighting shall work. Test button is broken, location of lighting breaker is unknown. | |
| Missouri Minimum : Platform Lifts | (U) - Existing Vertical and Inclined Platform Lifts | (U)1 (Re-Inspect) | Yes | No | Pit stop switch and housing are damaged. Repair and re-test | |
| Missouri Minimum : Platform Lifts | (U) - Existing Vertical and Inclined Platform Lifts | (U)1 | Yes | No | Electrical box in pit area is pulled from wall and damaged. Wiring is exposed. Repair as needed. |