Inspection
Inspection Details
Equipment ID
16565
16565
Inspection Date
8/17/2021
8/17/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
365
365
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
2d092fde-4ae7-4339-b30d-f06e23bcc775
2d092fde-4ae7-4339-b30d-f06e23bcc775
Location
Brookside Apartments
1602 BROOKSIDE DR, SAINT JOSEPH, MO
Phone: (816) 232-4353
1602 BROOKSIDE DR, SAINT JOSEPH, MO
Phone: (816) 232-4353
Owner
Attn: ARK Capital Brookside, LLC
ARK Capital Brookside, LLC
1602 Brookside, #214, St. Joseph, MO 64506
Phone: (816) 279-2363
Email: ARKbrookside@yahoo.com
ARK Capital Brookside, LLC
1602 Brookside, #214, St. Joseph, MO 64506
Phone: (816) 279-2363
Email: ARKbrookside@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Fire service phase 1 keyswitch needs to designate "ON-OFF-BYPASS" positions. No designation present and keyswitch spins around due to loose mounting. | 10/3/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not provide two way conversation. Call connects to voicemail message. | 8/17/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavenger pump from pit. Cylinder drain lines need to be ran to pit collection containers of no more than 5 gallon capacity. | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide maintenance records of procedures per maintenance control plan. | 1/16/2026 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Test and log firefighter operation monthly | 1/16/2026 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Need to provide firefighter key on site. | 1/16/2026 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room access door needs to be self locking and non-defeatable | 1/16/2026 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Test and log firefighter operation monthly | 1/16/2026 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside the machine room | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Identify the inside of hoistway doors with a numeral corresponding to the landing floor | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replacement for identification marking on hall firefighter keyswitch needs to be of equivalent material and design as the original bezel. Handwritten marking on a piece of tape stuck on the wall does not meet this requirement. | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | emergency phone does not operate | 1/16/2026 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Install guarding over car light fixtures | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Post In Case of Fire signage at each landing next to hall call station | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Identity inside of hoistway door with a numeral corresponding to the landing floor | 1/16/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | Remove hydraulic oil from pit floor | 1/16/2026 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | IN CAR EMERGENCY PHONE NOT WORKING |