Inspection
Inspection Details
Equipment ID
24267
24267
Inspection Date
7/26/2021
7/26/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Kevin Crossland
Kevin Crossland
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
e6f66fd1-c3a1-40b0-b382-2a86da990ffc
e6f66fd1-c3a1-40b0-b382-2a86da990ffc
Location
MSSU-Nixon Hall
3950 E Newman Road, Joplin, MO
Phone: (000) 000-0000
3950 E Newman Road, Joplin, MO
Phone: (000) 000-0000
Owner
Attn: Bob
MSSU
3950 NEWMAN RD, JOPLIN, MO 64801
Phone: (417) 625-9343
MSSU
3950 NEWMAN RD, JOPLIN, MO 64801
Phone: (417) 625-9343
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no certificate on site | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | 8.11.2.1.1(e) (RD)one ceiling panel missing needs replaced | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | machine room door will not lock when door is shut | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone will not call out | 7/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | Cab lighting shall be guarded to prevent breakage. Ceiling panel missing, exposing glass lamps | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. Door sticks. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | Yes | No | Cab lighting shall be guarded to prevent breakage. Ceiling panel missing, exposing glass lamps(2020, 2021, 2022 Violation) | 6/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Machine room door shall be self-closing and self-locking. Door sticks.(2020, 2021, 2022 Violation) | 6/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | No | No | Non-elevator related items shall not be stored in Machine Room. (Carpet Shampooer being stored in Equipment room) |