Inspection
Inspection Details
Equipment ID
15854
15854
Inspection Date
8/12/2021
8/12/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
9a6dd533-0c90-41d0-b10e-3070d68e00e5
9a6dd533-0c90-41d0-b10e-3070d68e00e5
Location
Frontier Middle School
9233 HIGHWAY DD, O FALLON, MO
Phone: (636) 327-3858
9233 HIGHWAY DD, O FALLON, MO
Phone: (636) 327-3858
Owner
Attn: Linda Bagby
Wentzville R-IV School District
1 Campus Dr, Wentzville, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Wentzville R-IV School District
1 Campus Dr, Wentzville, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | One cab light bulb is not working. | 2/24/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab light bulbs shall be guarded to contain glass if light breaks. | 2/24/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | The inside of the cab shall be labeled as "Elevator #1". | 2/24/2020 |
| A17.1-1996 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 1001.2(b)(10) | No | No | The first floor elevator entrance shall be labeled as "Elevator #1". | 2/24/2020 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | Yes | Door closing force exceeded maximum allowed. RED TAGGED | 8/24/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light shall work, may need battery replacement. | 8/24/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone did not provide 2 way communication. May need to be reprogrammed. | 8/24/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and must have a cat 5 weight test performed within 90 days or less | 8/24/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Unsealed | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide phone to work | 7/20/2022 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 111 | No | No | Door restrictor out of adjustment. | 3/8/2024 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV unsealed, provide testing. | 7/24/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(b) | No | No | Provide current year documents for the MCP. | 3/8/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 3/8/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone line not working | 6/20/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post current certificate in machine room | 3/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed or tagged. Perform required test on OSV within 90 days. Re-inspection required | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/4/2026 |