Inspection
Inspection Details
Equipment ID
2049
2049
Inspection Date
8/20/2021
8/20/2021
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Seth Dunbar
Seth Dunbar
Relief Valve Pressure
375
375
Slide
Governor Rope Pull
Door Closing Force
F-22 R-20
F-22 R-20
External ID
8e623b29-ab42-47c5-af89-331f0efe45d4
8e623b29-ab42-47c5-af89-331f0efe45d4
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Lee's Summit R-7 School District
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency lights weak. | 1/19/2021 | |
A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3 | x | no metal data tags | 1/19/2022 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Machroom door lock defeatable | 1/19/2022 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | FFS modules in machine room missing covers. | |||
A17.1-2016 : Elevators | 2.14 - Code data plate | 8.11.2.1.2(hh) | Provide code data plate in machine room. | |||
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.2.1.1(r) | x | Provide door restrictors for each car door. | 1/19/2023 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(k) | Smoke and heat detector wiring exposed, not in conduit. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Provide covers for FFS modules in machine room. | 9/26/2023 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | New smoke detectors present in machine room, but not connected to controller. | 9/26/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency battery lowering not working. Battery | 4/1/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Top of hoistway smoke recalls to wrong floor | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip not overriding battery lowering. Need relay added | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emergency battery lowering inoperable. Bad battery | 2/20/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip battery override needs testing with good battery | 2/20/2024 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | x | Shunt trip not overriding emergency battery lowering | 10/28/2024 |