Inspection
Inspection Details
Equipment ID
2327
2327
Inspection Date
8/23/2021
8/23/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jeffrey Borgeson
Jeffrey Borgeson
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
a3667b1c-318b-49a7-8753-1ca6a0999beb
a3667b1c-318b-49a7-8753-1ca6a0999beb
Location
Housing Unit #10
3401 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 387-2158
Email: linda.weis@doc.mo.gov
3401 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 387-2158
Email: linda.weis@doc.mo.gov
Owner
Attn: INTERAGENCY
WRDCC-INTERAGENCY
3401 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (000) 000-0000
WRDCC-INTERAGENCY
3401 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency bell does not operate | 7/22/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove water and oil from pit. Pits need to be kept dry. | 4/8/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not operate. | 4/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate. | 11/8/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/8/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Exposed door motor leads need to be in metal conduit | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain line needs to drain into pit collection container. | 9/8/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water and oil mixture from pit. Pit needs to be kept clean and dry. | 9/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not override security. 14 days to repair or red tagged. May apply for variance from the state. | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | Yes | Replace plunger seal. Plunger seal blew out during pressure relief testing. | 4/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 4/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MRL not up to date | 4/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed. | 4/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | COVER HOLE IN PIT FLOOR | 8/8/2024 |