Inspection
Inspection Details
Equipment ID
3323
3323
Inspection Date
8/17/2021
8/17/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
53880e73-c664-4f43-a16d-e3c34753c6e7
53880e73-c664-4f43-a16d-e3c34753c6e7
Location
AmeriStar Casino
1 AMERISTAR BLVD, SAINT CHARLES, MO
Phone: (636) 940-4340
1 AMERISTAR BLVD, SAINT CHARLES, MO
Phone: (636) 940-4340
Owner
Attn: AmeriStar Casino- St. Charles LLC
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
Billing
Attn: AmeriStar Casino- St. Charles, LLC
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lights. | 7/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher needs to be serviced. 2.7.1 | 7/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell not working. | 8/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone drops connection during call. | 6/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Monthly firefighters service log shall be maintained on site | 10/22/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | 3rd landing is missing 2 door gibs. REINSPECT REQUIRED | 10/22/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | 2nd landing is missing 1 door gib. REINSPECT REQUIRED | 10/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 11/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | A car door restrictor bracket is missing on the 3rd floor and shall be reinstalled so that the door restrictor will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 11/21/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in cab is not working. Re-inspection required | 8/23/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The elevator has an emergency backup generator that is used in case of a power outage, this system needs to be tested. Re-inspection required | 8/23/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide Cat 1 testing. | 10/29/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide Cat 1 testing. | 10/29/2024 |