Inspection
Inspection Details
Equipment ID
24668
24668
Inspection Date
8/20/2021
8/20/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
1fa4034c-6cb4-4d36-8b72-de3df301707b
1fa4034c-6cb4-4d36-8b72-de3df301707b
Location
Tthe Georgian
1418 Carroll St, St. Louis, MO
Phone: (314) 667-5913
Email: bhansen@rainericonstruction.com
1418 Carroll St, St. Louis, MO
Phone: (314) 667-5913
Email: bhansen@rainericonstruction.com
Owner
Attn: Shawndale Carson
HG Pear Georgian, LLC
919 N. East Street, Indianapolis, IN 46202
Phone: (314) 200-4278
Email: invoices@rainericonstruction.com
HG Pear Georgian, LLC
919 N. East Street, Indianapolis, IN 46202
Phone: (314) 200-4278
Email: invoices@rainericonstruction.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 8/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car shall work, appears not to have a live phone line. Re-inspection required | 5/9/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 6/18/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 5/6/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Battery lowering unit is inoperable. Repair or replace. REINSPECT IN 14 DAYS | 6/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, needs repaired. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator had power issue, could not complete inspection. Need to perform the following tests to complete the inspection: all hoistway tests, overspeed valve testing & fire service. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/6/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Battery lowering unit is inoperable. Repair or replace. REINSPECT IN 14 DAYS | 5/6/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Battery lowering unit is inoperable. Repair or replace. REINSPECT IN 14 DAYS | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, needs repaired. Re-inspection required |