Inspection
Inspection Details
Equipment ID
2330
2330
Inspection Date
8/23/2021
8/23/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jeffrey Borgeson
Jeffrey Borgeson
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
3b477e2b-e53d-47f5-96e4-acb58613d06e
3b477e2b-e53d-47f5-96e4-acb58613d06e
Location
Housing Unit #11
3401 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 387-2158
3401 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 387-2158
Owner
Attn: INTERAGENCY
WRDCC-INTERAGENCY
3401 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (000) 000-0000
WRDCC-INTERAGENCY
3401 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Photo eye door reopening device does not function. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Fire extinguisher in machine room has expired certification. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Provide fire service instructions inside and outside elevator. | 2/22/2023 |
| conversion | conversion | n/a | No | No | emergency car light and bell do not operate. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Emergency car light and bell not working | 2/22/2023 |
| conversion | conversion | n/a | No | No | Post fire service instructions inside elevator | 2/22/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter instructions next to hall fire keyswitch. Presently has phase 2 instructions next to hall fire keyswitch. | 2/22/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not overide security for bottom floor car call. 14 days to repair or red tagged. | 8/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light does not operate. | 8/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | No emergency signal device. Emergency bell does not operate and no phone present on elevator. | 8/23/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not override security for bottom floor car call. 14 days to repair or red tagged, may apply for variance from the state. | 9/8/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lighting. Not all machine room light fixtures illuminate | 2/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 2/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MRL not up to date | 2/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/22/2023 |