Inspection
Inspection Details
Equipment ID
6485
6485
Inspection Date
9/2/2021
9/2/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Matthew Toettcher
Matthew Toettcher
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
26/28
26/28
External ID
f090a0c4-ec5d-4159-99c1-a1a630333833
f090a0c4-ec5d-4159-99c1-a1a630333833
Location
New Life Pentecostal Church
11570 Mark Twain Ln, Bridgeton, MO
Phone: (314) 291-4181
11570 Mark Twain Ln, Bridgeton, MO
Phone: (314) 291-4181
Owner
Attn: New Life Pentecostal Church
New Life Pentecostal Church
11570 Mark Twain Ln, Bridgeton, MO 63044
Phone: (000) 000-0000
Email: churchoffice@newlifestlouis.com
New Life Pentecostal Church
11570 Mark Twain Ln, Bridgeton, MO 63044
Phone: (000) 000-0000
Email: churchoffice@newlifestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Right side jack needs repacking, pit full of oil | 11/3/2020 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 3/26/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 3/26/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove all non elevator storage from machine room | 3/26/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Provide a MCP to include prints | 9/20/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Repair emergency light in the car | 4/18/2022 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 3/26/2025 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Repair battery lowering unit..not working | 9/24/2024 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Repair machine room lighting | 3/26/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Remove al non elevator storage from the machine room | 3/26/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in the machine room | 3/26/2025 | ||
| MO Minimum : Elevators | (D) - Brakes | (D)1 | x | x | Repair east jack---leaking packing | 12/12/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Make emergency battery lowering unit operational | 12/12/2024 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Replace missing phase 1 fire instructions at L level | 3/26/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 3/26/2025 |