Inspection
Inspection Details
Equipment ID
6584
6584
Inspection Date
9/7/2021
9/7/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
3751a582-93c7-4f78-9214-9e3a37e5da70
3751a582-93c7-4f78-9214-9e3a37e5da70
Location
FW Logistics
303 Rock Industrial Park Drive, Bridgeton, MO
Phone: (314) 250-9450
Email: tim.wadley@am.jll.com
303 Rock Industrial Park Drive, Bridgeton, MO
Phone: (314) 250-9450
Email: tim.wadley@am.jll.com
Owner
Attn: Tim Wadley
FW Logistics
303 Rock Industrial Park Drive, Bridgeton, MO 63044
Phone: (314) 250-9450
Email: tim.wadley@am.jll.com
FW Logistics
303 Rock Industrial Park Drive, Bridgeton, MO 63044
Phone: (314) 250-9450
Email: tim.wadley@am.jll.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide a maintenance control program on site posted on controller | 9/24/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Service fire extinguisher at the machine room | 9/24/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | make phone operational | 9/7/2021 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 9/24/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Repair phone in car | 10/4/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Provide complete maintenance control program to include prints | 9/24/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide a maintenance control plan to include prints | 9/24/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | More light is needed inside the car. The minimum illumination at the car threshold, with the door closed, shall be not less than 5 foot-candles for passenger elevators. | 9/24/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current ABC type fire extinguisher shall be provided in the machine room. | 9/24/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Cited multiple years. Last certificate expired 9/21/2020. | 10/3/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | More light is needed inside the car. The minimum illumination at the car threshold, with the door closed, shall be not less than 5 foot-candles for passenger elevators. Previously cited. Potential re-inspection item if not corrected. | 10/3/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | Provide complete maintenance control program to include prints. Previously cited. Potential re-inspection item if not corrected. | 10/3/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Jack drain tube to be routed to a measurable container in pit. Currently, 1 drain tube drains directly into tank. | 10/3/2025 |