Inspection
Inspection Details
Equipment ID
11408
11408
Inspection Date
8/31/2021
8/31/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
b80b71bf-6413-4558-b569-7a94281c90b3
b80b71bf-6413-4558-b569-7a94281c90b3
Location
IBM- Bldg 306
325 James S McDonnell Blvd, Hazelwood, MO
Phone: (314) 234-6282
325 James S McDonnell Blvd, Hazelwood, MO
Phone: (314) 234-6282
Owner
Attn: IBM- St. Louis
IBM- St. Louis
325 James S McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
IBM- St. Louis
325 James S McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
Billing
Attn: CBRE Managed Services Inc
CBRE Managed Services Inc
325 James S McDonnell Blvd, Hazelwood, MO 63042
Phone: (314) 252-6228
Email: John.Roberts@cbre.com
CBRE Managed Services Inc
325 James S McDonnell Blvd, Hazelwood, MO 63042
Phone: (314) 252-6228
Email: John.Roberts@cbre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Replace broken step tread. Rule 7.9 | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Starting key switch needs to be replaced. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Need to do step indexing. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Replace broken step tread. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(H) | No | No | Lower embark light not working. | 2/1/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Observed broken tread on one step. | 2/1/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Broken fin on step tread, replace tread. Re-inspection required | 4/13/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair non working lower left embarkation light. Re-inspection required | 4/13/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | A copy of the MCP shall be kept in the machine room | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Observed broken tread on step, replace. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.6.2(i) Step Demarcation | No | No | Lower left embarkment light not working. | 5/23/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current State Elevator Certificate. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | Yes | Brake test failed, unit removed from service. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean upper and lower pit pans. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.6.2(i) Step Demarcation | No | No | Lower left light not working. | 5/23/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current Certificate. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Observed broken tread on step, replace. | 5/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean both pit pans. | 5/23/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair non working lower left embarkation light. Reported as fixed 5/23/2023 but still existing, re-inspection required. | 4/1/2026 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a non-combustible frame with a clear protective vision plate over it. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log testing logs, etc. Missing MCP for 2022, 2023, & 2024. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean upper pit pan. Excessive metal shaving from steps. Investigate cause, repair, and clean. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair non working lower left embarkation light. Recurring violation/Multiple violation citations, CITED 2025,2023,2022, 2021 | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Step Tread damaged on trailing edge of 1 step. Damaged steps treads should be replaced to conform | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean Upper Pit Pan. |