Inspection
Inspection Details
Equipment ID
11093
11093
Inspection Date
9/3/2021
9/3/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
30"
30"
Governor Rope Pull
100/670
100/670
Door Closing Force
25
25
External ID
22542b13-acb7-4aca-9d6d-e66cfda13e16
22542b13-acb7-4aca-9d6d-e66cfda13e16
Location
Grandview Tower
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
Owner
Attn: Grandview Apartment Homes LLC
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Billing
Attn: Grandview Apartment Homes LLC % The Wellington Group
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | The counterweight is within 1 inch of touching the oil buffer when the elevator travels to the top floor. The counterweight buffer has a buffer switch that will activate when the oil buffer is compressed thereby resulting in a elevator shut down. The hoist ropes shall be shortened to provide a minimum runby of 6 inches. | 5/14/2020 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Provide annual testing of elevator recall and power selector switch on standby power operation. | 2/17/2021 | |
A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 1001.2(e)(2) | x | Provide current code compliant runby | 9/14/2022 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean pit | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Provide cat 5 generator test | 9/14/2022 | |
A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | Provide testing of generator selector switch | |||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Hoistway door missing bottom door guide, 10th floor left door | |||
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | Clean car top | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Provide phase 1 and 2 testing | 9/14/2022 | |
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Door restrictor inoperable. Re-inspection required | 3/8/2023 | |
A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | x | Runby shall be adjusted to maintain at least 6" of runby. Re-inspection required | 3/8/2023 | |
MO Minimum : Elevators | (A) - Hoistways | (A)3 | Fire tabs shall be installed on 1st floor doors | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be cleaned, including hoistway & cartop | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be on display in the machine room | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule for emergency power test. Re-inspection required | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated Missouri Operating Certificate in machine room |