Inspection
Inspection Details
Equipment ID
11094
11094
Inspection Date
9/3/2021
9/3/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
26"
26"
Governor Rope Pull
100/640
100/640
Door Closing Force
15
15
External ID
5e8f4914-c7d6-4edb-86c5-9c2f2c8536c5
5e8f4914-c7d6-4edb-86c5-9c2f2c8536c5
Location
Grandview Tower
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
Owner
Attn: Grandview Apartment Homes LLC
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Billing
Attn: Grandview Apartment Homes LLC % The Wellington Group
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide annual testing of elevator recall and power selector switch on standby power operation. | 2/17/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Provide cat 5 generator test | 9/14/2022 |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | No | No | Provide testing of generator selector switch | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Hoistway door missing bottom door guide, 1st floor left door | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Clean car top | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Provide phase 1 and 2 testing | 9/14/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work | 9/14/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 3/8/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be cleaned | |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Fire tabs shall be re-installed on 1st floor doors | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Car top needs cleaning | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule emergency power test. Re-inspection required | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work when loss of normal power | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display Updated Missouri Operating Certificate in machine room |