Inspection
Inspection Details
Equipment ID
11094
11094
Inspection Date
9/3/2021
9/3/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
26"
26"
Governor Rope Pull
100/640
100/640
Door Closing Force
15
15
External ID
5e8f4914-c7d6-4edb-86c5-9c2f2c8536c5
5e8f4914-c7d6-4edb-86c5-9c2f2c8536c5
Location
Grandview Tower
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
300 S Grand Blvd, St. Louis, MO
Phone: (314) 984-9700
Owner
Attn: Grandview Apartment Homes LLC
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Grandview Apartment Homes LLC
300 S Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Email: adower@twgstl.com
Billing
Attn: Grandview Apartment Homes LLC % The Wellington Group
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Grandview Apartment Homes LLC
1715 Deer Tracks Trl, Ste 220, St. Louis, MO 63131
Phone: (314) 984-9700
Email: lmoore@twgstl.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Provide annual testing of elevator recall and power selector switch on standby power operation. | 2/17/2021 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean pit | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Provide cat 5 generator test | 9/14/2022 | |
A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | Provide testing of generator selector switch | |||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Hoistway door missing bottom door guide, 1st floor left door | |||
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | Clean car top | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Provide MCP | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Provide phase 1 and 2 testing | 9/14/2022 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide existing phone to work | 9/14/2022 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working. Re-inspection required | 3/8/2023 | |
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be cleaned | |||
MO Minimum : Elevators | (A) - Hoistways | (A)3 | Fire tabs shall be re-installed on 1st floor doors | |||
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | Car top needs cleaning | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be on display in the machine room | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule emergency power test. Re-inspection required | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone is not working. Re-inspection required | ||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work when loss of normal power | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display Updated Missouri Operating Certificate in machine room |