Inspection
Inspection Details
Equipment ID
2693
2693
Inspection Date
7/28/2021
7/28/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
25e8c9ed-165b-4f8d-a583-3fb99a86c521
25e8c9ed-165b-4f8d-a583-3fb99a86c521
Location
Miller Nichols Library
800 E 51ST ST, KANSAS CITY, MO
Phone: (816) 235-1363
800 E 51ST ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Repair/Replace check valve, elevator settled more than 2 inches in 15 minutes. closed the gate valve in the machine room and the elevator did not move at all in 15 minutes | |||
conversion | conversion | n/a | pit light is not bright enough, it does not put out 100 lux. Check that correct light bulb is installed in fixture | |||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | replace emergency light battery, it is dead | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | clean up oil in pit and replace leaking vic couplers | 5/28/2020 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current copy of the state operating certificate in the machine room | |||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Post monthly fire service test log in the machine room | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide access to the complete MCP in the machine room according to 8.6 | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Machine room fire extinguisher inspection tag expired | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | the machine room fire extinguisher was last tagged in 2015, have the fire extinguisher inspected and tagged annually | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. The one there is from 2014 | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Maintenance Control Program documents are missing | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27 | x | x | The fire service phase 1 keyswitch would not rest the elevator, could not put the elevator back in normal operation at the keyswitch, had to reset it from the controller. all other aspects of fire service worked. | 7/28/2021 |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2015 | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | replace the emergency light battery, it is dead | 5/29/2024 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Replace the emergency light battery it is dead | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Recovery pump in the pit needs to be replaced with a 5 gallon bucket per state memo 6 (8.6.5.5.2) | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | Clean up oil on pit floor | ||
A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | Machine room door lock is not engaging with the door jam, repair machine room door so it will self lock |