Inspection
Inspection Details
Equipment ID
14482
14482
Inspection Date
9/9/2021
9/9/2021
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Keith Tynes, Jr
Keith Tynes, Jr
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
External ID
51d939df-a00a-42e3-9b6c-4d4a664b3b0b
51d939df-a00a-42e3-9b6c-4d4a664b3b0b
Location
Cardinal Ritter College Prep
701 N Spring Ave, St. Louis, MO
Phone: (314) 416-5500
701 N Spring Ave, St. Louis, MO
Phone: (314) 416-5500
Owner
Attn: Cardinal Ritter College Prep
Cardinal Ritter College Prep
701 N Spring Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Stephenludwig@archstl.org
Cardinal Ritter College Prep
701 N Spring Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Stephenludwig@archstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean oil soaked pads in pit and adjust left side jack to drain to recovery method. | 9/11/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | OIL SOAKED MATS IN PIT; LEFT OIL RECOVER LINE LEAKING INTO PIT 9/11/2019 | 4/2/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed. Test, tag and seal upon completion. | 6/14/2022 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | No | No | Provide code compliant means of oil collection in pit. | 6/15/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency battery back up system not working. Repair/replace as needed. | 6/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits to be cleaned of oil & oil filled pads | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 2/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove oil from pit | 2/11/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working, needs repaired. Re-inspection required | 6/13/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Repair / replace non working sump pump in pit. | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace broken stop switch on door operator. | 2/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned if oil and oil filled pads | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be in the machine room for each unit | 2/11/2026 |