Inspection
Inspection Details
Equipment ID
13902
13902
Inspection Date
9/14/2021
9/14/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
2aab9a96-d1fa-44a9-9fbe-6bf839f827a5
2aab9a96-d1fa-44a9-9fbe-6bf839f827a5
Location
George Bode Middle School
720 N NOYES BLVD, SAINT JOSEPH, MO
Phone: (816) 671-4050
720 N NOYES BLVD, SAINT JOSEPH, MO
Phone: (816) 671-4050
Owner
Attn: Danny Brush
St. Joseph School District
1000 S 9TH ST, SAINT JOSEPH, MO 64503
Phone: (000) 000-0000
Email: Danny.brush@sjsd.k12.mo.us
St. Joseph School District
1000 S 9TH ST, SAINT JOSEPH, MO 64503
Phone: (000) 000-0000
Email: Danny.brush@sjsd.k12.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Car lighting illuminates insufficiently. | 1/5/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 12/18/2020 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | Cylinder drain line needs to drain into pit container of no more than a 5 gallon container | 1/5/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not illuminate | 7/13/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 7/13/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not provide two way conversation. Phone dials out but there is no answer. | 7/17/2023 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Post In Case of Fire signage next to hall button fixture at each landing | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed in machine room | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone does not operate | 7/29/2024 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Car lighting disconnect is not lockable in the open position | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | FIRE RATE TOP OF MACHINE ROON | 8/15/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.3 Device Actuation at Recall Level | Yes | Yes | BUILDING NEEDS TO ADD ANOTHER FIRE SERVICE RELAY TO SEPERATE THE DETECTORS IN THE MACHINE ROOM FROM THE TOP OF THE HOISTWAY | 8/15/2024 |