Inspection
Inspection Details
Equipment ID
20652
20652
Inspection Date
9/8/2021
9/8/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
Slide
Instant
Instant
Governor Rope Pull
150/270
150/270
Door Closing Force
22
22
External ID
e67cca37-0a3b-4e08-885a-20e3b85ea58a
e67cca37-0a3b-4e08-885a-20e3b85ea58a
Location
Stifel Theatre
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
1400 Market St, St. Louis, MO
Phone: (314) 499-7701
Owner
Attn: Adrian Silverstein
Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Billing
Attn: Scottrade Center
Stifel Theatre
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Stifel Theatre
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Email: QReed@StlBlues.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Replace missing conduit in bottom of pit. | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction, needs to be replaced. Re-inspection required | 9/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in the machine room is expired, have serviced or replaced | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform no load testing of car safeties after safety drum rope is replaced with proper material. Re-inspection required | 9/15/2023 |
| A17.1-2016 : Elevators | 11.11 - Emergency Brake | 2.19.3 | Yes | No | Emergency brake failed to stop car within allowable distance (48") when performing un-intended movement test, repair & re-test. Re-inspection required | 9/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the emergency power selector switch. This is found next door in the security office. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct speed on the cross head data plate. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Numerous ledges in the hoistway exceeding code required 4”, repair as needed. | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 4/10/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 4/10/2026 |