MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Repair inoperative car safety operated switch linkage. Repair within 30 days or elevator shall be red tagged.
|
3/14/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative phone.
|
3/14/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
EMERGENCY PHONE NOT WORKING; CHECK LINE/ PHONE
|
5/6/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
Inactive per owners request after Maintenance provider refused to work on unit.
|
5/6/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
With Full Load at upper floor car sent down and went through slowdown and hit the buffers.
|
3/11/2026
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Governor as tripped using a rope at the lower floor due to the motor not being able to lift the car off the safeties during a soft set.
|
3/11/2026
|
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
It could not be determined if the car safeties linkage and shoes were wedged once set or if it was due to the motor not being able to pull off the safetiues during a soft set.
|
3/11/2026
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
4th floor landing, hoistway door could not be opened with the door operator or manually. Door hanger dropped down and door is wedgedon the sill.
|
3/11/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
All testing to be IAW applicable ASME code adopted and amended by the Elevator Safety Board, governor has to be physically tripped at the governor location.
|
3/11/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.100 State Operating Certificate and Local Operating Certificate (Revocation)
|
(5)(C) Revocation of State Operating Certificate.
|
x
|
x
|
Elevator was red tagged 9/15/2021 and placed out of service, state input wrong information (showed wrong inspector on state site) and allowed elevator to be worked on without properly getting red tag removed. Original red tag was on site and removed when I arrived.
|
3/11/2026
|