Inspection
Inspection Details
Equipment ID
14849
14849
Inspection Date
8/27/2021
8/27/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
74f789c7-e827-4573-9783-1ebf28a1dee1
74f789c7-e827-4573-9783-1ebf28a1dee1
Location
Landsdowne Medical Bldg
6651 Chippewa St, St. Louis, MO
Phone: (000) 000-0000
6651 Chippewa St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Landsdowne Medical Bldg
Landsdowne Medical Bldg
6651 Chippewa, SAINT LOUIS, MO 63109
Phone: (000) 000-0000
Landsdowne Medical Bldg
6651 Chippewa, SAINT LOUIS, MO 63109
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.5.8 - Single bottom jack. | 2/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than (10) foot-candles at floor level. | 2/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 2/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The permanent lighting fixture in the pit shall have a switch that is accessible from the pit access door. | 2/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Need to determine if this unit has a single bottom jack. If the jack is single bottom type it is required to be replaced, or a governor with safeties installed, or a plunger gripper installed on the unit. Documentation shall be available on-site about the jack type. | 2/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/30/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room needs more light. Lighting in the machine room shall be not less than 10 foot-candles at floor level. | 2/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired.An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: Extinguisher is expired. | 2/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove the oil from the pit floor. | 2/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Unit is running with the car and hoistway doors in the open position. Elevator locked out by maintenance company until violation is corrected. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Unit has been placed out of service. |