Inspection
Inspection Details
Equipment ID
2807
2807
Inspection Date
9/17/2021
9/17/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
2ab3bf93-409b-45c9-a9e9-881f32990fe1
2ab3bf93-409b-45c9-a9e9-881f32990fe1
Location
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO
Phone: (636) 947-5000
Email: michelle.deckard@ssmhealth.com
300 1st Capitol Dr, St. Charles, MO
Phone: (636) 947-5000
Email: michelle.deckard@ssmhealth.com
Owner
Attn: Samantha Bley
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
Email: Samantha.Bley@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
Email: Samantha.Bley@ssmhealth.com
Billing
Attn: Michelle Deckard
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5369
Email: michelle.deckard@ssmhealth.com
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5369
Email: michelle.deckard@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)8 | Yes | Yes | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the mechanical and electrical protection devices would not activate within the required limits. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 10/31/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. | 11/25/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. | 11/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Top of elevator cartop needs to be cleaned | 10/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on top of car needs to be replaced | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on bottom of counterweights needs to be replaced | 10/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace missing anti rotation cable on rear counterweight shackles. Re-inspection required | 12/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Machine is leaking oil excessively, need to repair leaks | 10/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing of the following equipment needs to be performed to complete the 5 year inspection: safeties pull out, overspeed governor rope pull thru, overspeed governor speed switch and jaw speeds, full load, full speed safeties, full load full speed car buffer, 125% capacity brake, no load full speed counterweight buffer. Test tags must also be filled out and applied to applicable equipment. Re-inspection required.t | 12/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Re-inspection required | 12/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Re-inspection required | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Top of elevator needs to be cleaned | 10/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in pit shall work | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on top of car needs to be replaced | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on bottom of counterweights needs to be replaced | 10/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to replace missing anti rotation cable on rear counterweight shackles. Re-inspection required | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Machine is leaking oil excessively, need to repair leaks | 10/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Tests of the following equipment need to be performed to complete Cat 5 inspection: safeties pull out, overspeed governor rope pull thru, overspeed governor speed switch and jaw speeds, full load full speed safeties, full load full speed safeties, full load full speed car buffer, 125% capacity brake, no load full speed counterweight buffer. Test tags must also be filled out and applied to applicable equipment. Re-inspection required | 10/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Top of elevator cartop needs to be cleaned | 11/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on top of car needs to be replaced | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on bottom of counterweights needs to be replaced | 11/5/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to replace missing anti rotation cable on rear counterweight shackles. Re-inspection required | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Machine is leaking oil excessively, need to repair leaks | 11/5/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell in car shall work. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Top of elevator cartop needs to be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on top of car needs to be replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Guide roller bushing on bottom of counterweights needs to be replaced | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to replace missing anti rotation cable on rear counterweight shackles. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Machine is leaking oil excessively, need to repair leaks |