Inspection
Inspection Details
Equipment ID
20093
20093
Inspection Date
8/25/2021
8/25/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
100/240
100/240
Door Closing Force
15
15
External ID
7f0936c5-4806-4549-805e-a7621e99a379
7f0936c5-4806-4549-805e-a7621e99a379
Location
Holiday Inn Express
4630 Lindell Blvd, St. Louis, MO
Phone: (314) 361-4900
4630 Lindell Blvd, St. Louis, MO
Phone: (314) 361-4900
Owner
Attn: UNK
Garrison St. Louis OP Co. LLC
1290 AVENUE OF THE AMERICAS STE 916, NEW YORK, NY 10019
Phone: (000) 000-0000
Garrison St. Louis OP Co. LLC
1290 AVENUE OF THE AMERICAS STE 916, NEW YORK, NY 10019
Phone: (000) 000-0000
Billing
Attn: Holiday Inn Express
Holiday Inn Express
4630 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 361-4900
Email: roberto@hiexpresscwe.com
Holiday Inn Express
4630 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 361-4900
Email: roberto@hiexpresscwe.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | The ceiling panel in the elevator cab has been removed, exposing the lighting. The cab lights shall be guarded. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept clean. Clean the pit. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | The alarm bell jewel is missing and shall be replaced. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall be kept clean. All equipment and materials not necessary for the operation or maintenance of the elevator shall not be stored in the machine room. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | No | No | The hoistway is in need of a clean down. Clean the hoistway. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be cleaned. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The top of the car shall be cleaned. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall be kept clean and all non-elevator related items shall be removed. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | The fire service switch for Phase 1 on the hall call station shall be repaired on the first floor. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/22/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All of the weight portion of the inspections has been completed. All other testing shall be completed due to running out of time. | 8/17/2026 |