Inspection
Inspection Details
Equipment ID
4904
4904
Inspection Date
8/20/2021
8/20/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Ronald Dennison
Ronald Dennison
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
fe16b2ef-6a70-41af-8ac7-985b70fc81fe
fe16b2ef-6a70-41af-8ac7-985b70fc81fe
Location
Oakwood Manor II
6000 N Oak Trfy, Gladstone, MO
Phone: (816) 455-1235
6000 N Oak Trfy, Gladstone, MO
Phone: (816) 455-1235
Owner
Oakwood Manor Condo
4770 N BELLEVIEW AVE STE 101, KANSAS CITY, MO 64116-2190
4770 N BELLEVIEW AVE STE 101, KANSAS CITY, MO 64116-2190
Billing
Attn: Oakwood Manor Condo Assn
4770 N BELLEVIEW AVE STE 101, KANSAS CITY, MO 64116-2190
4770 N BELLEVIEW AVE STE 101, KANSAS CITY, MO 64116-2190
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | emergecy phone line is dead, provide working phone line | 8/9/2019 |
| conversion | conversion | n/a | No | No | fire extinguisher inspection tag is from 2015, it is to be inspected annually | 8/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 8/6/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | the phone line for the emergency phone is dead, provide working phone to the elevator controller | 8/18/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, phone line dead | 8/20/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | fire service phase 2 instructions do not match operation, missing instructions for hold and automatic return to recall floor | 5/4/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out | 5/4/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone is not working, phone line is dead | 9/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2019, the extinguisher is to be inspected and tagged annually | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | need to have a copy of elevator wiring diagrams in the machine room | 5/4/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | the lower landing can not be secured by removing the button wiring on the car operating panel, the elevator shall be able to go to all landings when the elevator is in fire service operation, use a method to secure the bottom landing that can be overridden by fire service operation. | 9/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, no dial tone one the phone line, provide a working phone line | 9/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2019, the machine room fire extinguisher is to be inspected and tagged annually | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, no phone line, provide a working phone line | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) | Yes | No | the lower landing can not be secured by removing the wiring from both the hall button and the car button, fire service must be able to override security to access the lower landing, currently not able to access the lower landing on fire service | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | the top landing shall be illuminated so that when the elevator is in service the lighting shall be not less than 5 foot candles of illumination (110.10b) | 5/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag is from 2019, the extinguisher is to be inspected and tagged annually | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, no phone line, provide working phone line | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) | Yes | No | the lower landing can not be secured by removing the button wiring from both the hall button and car button, have to be able to run elevator to the lower landing on fire service, will have to secure the bottom landing with a keyswitch or other device that can be overridden by fire service. Must apply for variance to make the bottom landing as a pit access only | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Top landing needs to have a light that provides 5 foot candles of illumination at the hoistway door sill at all times (110.10b) |