Inspection
Inspection Details
Equipment ID
19088
19088
Inspection Date
8/2/2018
8/2/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
21
21
External ID
7f2043a1-3578-45b6-b9af-8c5a02e9e808
7f2043a1-3578-45b6-b9af-8c5a02e9e808
Location
The Cresent
153 CARONDELET PLZ, CLAYTON, MO
153 CARONDELET PLZ, CLAYTON, MO
Owner
The Crescent Condominium
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
Billing
Attn: The Crescent Condominium C/O Community Property Mgmt
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide on-site maintenance control program. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Car top outlet has open neutral, repair as needed. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Repair light at top of hoistway. | 6/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide code compliant runby (currently 1"). | 7/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Provide working Phase I operation and test Phase II. | 7/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Category 5 testing needs to be completed, was only able to conduct annual portion of test. | 7/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Provide for remote governor tripping to work | 6/2/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/2/2026 |
| A17.1-2016 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | No | No | The drop ceiling shall have some sort of access for emergency evacuation | 8/18/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency generator testing needs to be performed. Re-inspection required | 8/18/2026 |