Inspection
Inspection Details
Equipment ID
19439
19439
Inspection Date
8/2/2018
8/2/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
20
20
External ID
5ee41c12-41b3-4407-a159-bf9837d0b112
5ee41c12-41b3-4407-a159-bf9837d0b112
Location
The Cresent
153 CARONDELET PLZ, CLAYTON, MO
153 CARONDELET PLZ, CLAYTON, MO
Owner
The Crescent Condominium
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
Billing
Attn: The Crescent Condominium C/O Community Property Mgmt
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean pit. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | Car top outlet has open neutral, repair as needed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Light at top of hoistway does not work. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Car does not have emergency brake cable system. Provide and retest. | 7/5/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing needs to be completed, was only able to conduct the annual portion of test. | 7/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Hoistway access switch is not operating correctly at the 2nd floor. Re-inspection required | 9/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device has failed, needs repaired. Re-inspection required | 9/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Provide for counterweight derailment device to work |