Inspection
Inspection Details
Equipment ID
6832
6832
Inspection Date
9/30/2021
9/30/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
N/a
N/a
Governor Rope Pull
N/a
N/a
Door Closing Force
27
27
External ID
69002996-c8f1-4097-9900-f12641bc3f4f
69002996-c8f1-4097-9900-f12641bc3f4f
Location
The Ritz-Carlton
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
100 Carondelet Plz, St. Louis, MO
Phone: (314) 719-1445
Owner
Attn: Ritz Carlton Hotel
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Ritz Carlton Hotel
100 Carondelet Plz, St. Louis, MO 63105
Phone: (314) 863-6300
Email: rebecca.schwab@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Alarm bell on left hand Car Operating Panel when button or Stop switch is pressed | 11/28/2022 | ||
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | One of two emergency lamps is not working (right-hand COP). | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting is less than the required 19fc at controller. | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room outlets are not GFCI protected. | 6/26/2024 | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | x | Hoist Rope Tail retaining clips shall be properly spaced. | 6/26/2024 | |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Cartop needs 4" toe kick around perimeter under handrails. | 6/26/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 | x | Pit stop switch to be reachable from access door. | 6/26/2024 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit lighting is less than the required 10fc. | 6/26/2024 | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 3.26.1 | x | Mainline disconnect failed to trip when heat detector is activated. | 6/26/2024 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | x | x | Main floor smoke sent elevator to main floor. | 6/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test fire service phase 1 & 2. | 6/26/2024 | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | One of two emergency lamps is not working (right-hand COP). | 3/21/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting is less than the required 19fc at controller. | 3/21/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room outlets are not GFCI protected. | 3/21/2025 | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | x | Hoist Rope Tail retaining clips shall be properly spaced. | 3/21/2025 | |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.10.2.3 Toe Board | x | Cartop needs 4" toe kick around perimeter under handrails. | 3/21/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit lighting is less than the required 10fc. | 3/21/2025 |