Inspection
Inspection Details
Equipment ID
13544
13544
Inspection Date
9/16/2021
9/16/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
d452739c-da47-4292-bab1-7bac59464a8a
d452739c-da47-4292-bab1-7bac59464a8a
Location
Mallincrodt Bldg
3600 N 2ND ST, SAINT LOUIS, MO
Phone: (314) 654-1600
3600 N 2ND ST, SAINT LOUIS, MO
Phone: (314) 654-1600
Owner
Attn: Mallincrodt
Mallincrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Mallincrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Billing
Attn: Mallincrodt
Mallincrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Mallincrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current Mo state operating certificate in machine room | 12/10/2018 |
| conversion | conversion | n/a | No | No | Alarm bell not working | 12/10/2018 |
| conversion | conversion | n/a | No | No | Repair emergency phone | 12/10/2018 |
| conversion | conversion | n/a | No | No | Repair pit lighting/ lighting shall be permanent fixture | 12/10/2018 |
| conversion | conversion | n/a | No | No | Repair emergency lighting | 12/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone shall work with and without main power and give proper location. Walkie-talkie is not an approved elevator phone. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work and be of sufficient brightness. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Non-elevator related items shall not be stored in machine room. Remove Freon bottles, roofing adhesives, etc. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Test Incomplete. Standby Power operation to be tested and verified with 100% capacity. | 6/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Put light shall work, a permanent lighting fixture shall be provided in all pits. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work and be of sufficient brightness. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Standby power operation to be tested. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Front gate mechanical bump edge is not working. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light shall work. A permanent lighting fixture shall be provided in all pits. The light is not working. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Electrical box in machine room above light disconnect needs to have cover installed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.7 - Sequence operation | 2.13.3.4 | No | No | 2.13.3.4.1 - Freight door audible signal for "auto-close" is not working. Visual signal is working. |