Inspection
Inspection Details
Equipment ID
13344
13344
Inspection Date
9/29/2021
9/29/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
4
4
Governor Rope Pull
350/950
350/950
Door Closing Force
na
na
External ID
18b4978b-d626-4d51-bd64-219170a7b7bd
18b4978b-d626-4d51-bd64-219170a7b7bd
Location
Bevo Bottling Plant- Bldg #137
619 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 256-6278
619 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 256-6278
Owner
Attn: 137-2
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Anheuser Busch
1 Busch Pl, St. Louis, MO 63118
Phone: (314) 577-3998
Email: ryan.brohammer@anheuser-busch.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Repair sump pump | 9/26/2025 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Replace missing guards on machine room lights or provide tubes. | 9/26/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)5 | Yes | No | Repair or replace damaged control switches. | 9/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone | 9/29/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Replace missing guards on machine room lights or provide tubes | 9/26/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Replace cab light that has open wiring. Replace missing covers on cab lights | 9/26/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are undersized. Reinspect in 120 days | 1/12/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean all debris out of pit | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Bolt shut 8th floor rear door so that it will not open. Door is not in use | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Safety light ray does not work. Door will not reopen with something in the way. Reinspect Required | 9/26/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | In car rear door is off track and needs to be reattached and locked shut | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten hoist cables. Counterweight stricking buffers before final limit 14 day reinspection 11/14/23 | 10/17/2024 |