Inspection
Inspection Details
Equipment ID
8659
8659
Inspection Date
9/30/2021
9/30/2021
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
Slide
7
7
Governor Rope Pull
70/520
70/520
Door Closing Force
26
26
External ID
0b7dc926-6c8c-414e-927c-3ae4620b15c1
0b7dc926-6c8c-414e-927c-3ae4620b15c1
Location
Leonardo Bldg
4166 Lindell Blvd, St. Louis, MO
Phone: (888) 213-7363
4166 Lindell Blvd, St. Louis, MO
Phone: (888) 213-7363
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The cab lighting shall be properly guarded. | 12/15/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Replace the worn counterweight rollers. | 12/15/2019 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean and dry. | 12/15/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Replace the worn pick-up rollers at the 5th & 6th floor. | 12/15/2019 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | The car door restrictor shall be operational. | 11/25/2019 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Install an anti-spin device on the hoist ropes. | 11/25/2019 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are rouged and have reached minimum diameter in several areas. Replacement of the hoist ropes is required. | 11/25/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 12/2/2020 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current operating certificate in machine room. | 12/1/2020 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | All smoke detectors need to be tested | 10/15/2021 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Machine room shall be self closing and self locking | 10/15/2021 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | x | Grating in machine deck floor shall be fastened down or covered and fastened | 10/15/2021 | |
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Fire extinguisher in machine room needs replacing or servicing | 10/15/2021 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car shall work with failure indication and have battery backup for modem on phone line | 10/15/2021 | |
A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | x | Install code data plate containing all altered equipment code references to be installed on controller | 10/15/2021 | |
A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.10.2.2.5(b) | x | Runby signage shall be posted in pit | 10/15/2021 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Smoke detector in the elevator machine room shall flash the in car fire hat | 10/20/2021 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept dry and clear of debris | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency communication inoperable. Re-inspection required | 2/14/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete due to water in pit, safeties must be set. Re-inspection required | 2/14/2023 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Provide feeder location on the main line disconnect, in the elevator machine room.NEC620 | |||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Provide feeder location on the 110v. disconnect in the elevator machine room.NEC620 | |||
A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | Provide code compliant means to access secondary level in the elevator machine room. | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide existing phone to work. | 10/4/2024 | |
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Provide current year tested fire extinguisher in the elevator machine room. | |||
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | Sump pump in the pit is not working, repair/replace as needed. | 10/4/2024 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Remove water from the pit. | |||
A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | Door knob to access the machine room is damaged, replace. | |||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair inoperative emergency phone | ||
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Cab lighting shall be protected | |||
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Two lamps are required. Lamps shall operate independently of each other. | |||
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Cab lighting shall be wiring shall meet the NEC | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | Remove standing water from the elevator pit. |