Inspection
Inspection Details
Equipment ID
1917
1917
Inspection Date
7/16/2018
7/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
5128bb3c-19af-4d34-813b-6782035d1b1e
5128bb3c-19af-4d34-813b-6782035d1b1e
Location
Hilton at the Ballpark
1 S BROADWAY, SAINT LOUIS, MO
1 S BROADWAY, SAINT LOUIS, MO
Owner
Lodging Hospitality Management
111 WEST PORT PLZ STE 500, SAINT LOUIS, MO 63146-3015
111 WEST PORT PLZ STE 500, SAINT LOUIS, MO 63146-3015
Billing
Attn: Hilton at the Ballpark
1 S BROADWAY, SAINT LOUIS, MO 63102-1703
1 S BROADWAY, SAINT LOUIS, MO 63102-1703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.33 - Compensating ropes and chains | 1001.2(c)(30) | Yes | Yes | Replace compensation chain. Spliced at counterweight hitch. Red tagged elevator. | 1/30/2021 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | Yes | No | Governor fails to calibrate to original specifications. Repair/replace and retest. | 1/30/2021 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | Yes | No | Governor fails to calibrate to original specifications. | 2/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 2/29/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. | 1/13/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum diameter, need to replace the ropes within 90 days. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to machine room shall be clear and unobstructed. Need to remove all items in stairway leading to the machine room | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 2.8.1 | No | No | Traveling cable jacket has unrepaired breaks at the lobby. Need to repair or replace same | 3/25/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the non-elevator related items being stored in the machine room to provide proper room for maintenance to be performed. | 3/25/2026 |