Inspection
Inspection Details
Equipment ID
17302
17302
Inspection Date
10/8/2021
10/8/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
590
590
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
8d3e1ef2-ae01-4966-8b72-d8fca3444def
8d3e1ef2-ae01-4966-8b72-d8fca3444def
Location
Sunrise Assisted Living Center
13460 Manchester Rd, Des Peres, MO
Phone: (314) 965-3800
13460 Manchester Rd, Des Peres, MO
Phone: (314) 965-3800
Owner
Attn: Sunrise c/o Lerch Bates
Sunrise c/o Lerch Bates
9780 S Merifian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: sunrise.elevators@lerchbates.com
Sunrise c/o Lerch Bates
9780 S Merifian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: sunrise.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and needs to be tested with a category 5 weight test within 90 days or less | 8/27/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV is not sealed and must have a cat 5 weight test performed within 90 days or less | 8/27/2021 |
| A17.1-1996 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 303.3c | Yes | Yes | Hydraulic oil line fitting is leaking excessively, needs to be replaced. Red-tagged, Re-inspection required | 8/30/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform relief valve testing and 15 minute standing testing to complete inspection. Re-inspection required | 8/30/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery lowering device is not working. Re-inspection required | 8/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Phase I fire service bezel at key switch in lobby is illegible, needs to be replaced | 6/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform relief valve testing and 15 minute standing testing to complete inspection. Re-inspection required | 7/31/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery lowering device shall work. Re-inspection required | 7/31/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase I fire service bezel at key switch in lobby is illegible, need to replace | 6/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase I fire service bezel wording is missing, needs to be replaced | 6/20/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency battery lowering device is not working. Re-inspection required | 5/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed inside of the elevator Machine room. | 9/4/2025 |