Inspection
Inspection Details
Equipment ID
9769
9769
Inspection Date
10/5/2021
10/5/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Kevin Pajda
Kevin Pajda
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
3d7470a3-c378-41ad-869a-b59af7d3f5d8
3d7470a3-c378-41ad-869a-b59af7d3f5d8
Location
Broadway Tower
100 N Broadway, St. Louis, MO
Phone: (314) 421-0640
100 N Broadway, St. Louis, MO
Phone: (314) 421-0640
Owner
Attn: Sara Larson
100 Broadway Investors, LLC c/o Larson Commercial Real Estate, LLC
100 N Broadway, Ste 1100, St. Louis, MO 63102
Phone: (314) 421-0640
Alt Phone: (319) 213-1768
Email: sara.larson@larson-commercial.com
100 Broadway Investors, LLC c/o Larson Commercial Real Estate, LLC
100 N Broadway, Ste 1100, St. Louis, MO 63102
Phone: (314) 421-0640
Alt Phone: (319) 213-1768
Email: sara.larson@larson-commercial.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency bell shall work | 5/23/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1002.3d | Yes | No | Need to do 125% load test. | 8/1/2019 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)10 | Yes | No | Need to test car safeties. | 8/1/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Replace hoist ropes - two are stretched to maximum limit. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit lights that are out. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.10 - Compensating chains, ropes, and sheaves | 1001.2(e)(8) | Yes | No | Shorten compensating ropes. | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not work, needs repaired. Re-inspection required | 3/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Need to repair the car door restrictor to work. Re-inspection required | 3/14/2025 |