Inspection
Inspection Details
Equipment ID
17487
17487
Inspection Date
10/14/2021
10/14/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Healy
David Healy
Mechanic Name
David Reding
David Reding
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
67401a8b-50d2-4306-babd-6032553b70eb
67401a8b-50d2-4306-babd-6032553b70eb
Location
Burlington Retail Center
2401 BURLINGTON ST, NORTH KANSAS CITY, MO
Phone: (816) 252-3573
2401 BURLINGTON ST, NORTH KANSAS CITY, MO
Phone: (816) 252-3573
Owner
Attn: AKI Hickman LLC
AKI Hickman LLC
1509 W 12th St, Kansas City, MO 64101
Phone: (000) 000-0000
Email: brenda@unterseelaw.net
AKI Hickman LLC
1509 W 12th St, Kansas City, MO 64101
Phone: (000) 000-0000
Email: brenda@unterseelaw.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | No storage in machine room. | 10/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phone not working. | 10/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Provide guarding for overhead lighting in machine room. | 10/5/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Provide up to date fire extinguisher in machine room. | 10/5/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide up to date fire extinguisher in machine room. | 10/26/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machroom door lock is defeatable | 12/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 12/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | machroom door blocked by furniture an material draped over door | 12/7/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | extinquisher out dated expired | 12/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit lt not working | 12/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | need the machroom door to be self locking | 2/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 2/27/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | remove oil return lines fron cyl. head to tank | 2/27/2025 |