Inspection
Inspection Details
Equipment ID
25453
25453
Inspection Date
10/18/2021
10/18/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Andrew Smith
Andrew Smith
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
68e52e90-b52e-4a72-bf00-66ba8fd973d0
68e52e90-b52e-4a72-bf00-66ba8fd973d0
Location
Columbia Mennonite Guest House
4409 St. Charles Rd, Columbia, MO
Phone: (620) 664-4123
4409 St. Charles Rd, Columbia, MO
Phone: (620) 664-4123
Owner
Attn: Columbia Mennonite Guest House
Columbia Mennonite Guest House
4409 Saint Charles Rd, Columbia, MO 65201
Phone: (620) 664-4123
Email: columbiamennoniteguesthome@gmail.com
Columbia Mennonite Guest House
4409 Saint Charles Rd, Columbia, MO 65201
Phone: (620) 664-4123
Email: columbiamennoniteguesthome@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.4 | No | No | Provide electric/mechanical interlock for upper landing gate. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.4 | No | No | Provide electrical/mechanical interlock for lower landing door. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.6 | No | No | Running clearance between sill @ rear entrance under .375 inch minimum. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.7 | No | No | Clearance between platform guardrail and wall is 5 1/2". The tolerance is no less than 2", no more than 3". | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.1.1 | No | No | Provide solid enclosure of hoistway for entirety of hoistway. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.3 | No | No | Enclosure walls shall not deform more than one inch. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.11 - Emergency Signals | 2.11.1 | Yes | No | Provide audible alarm upon activation of emergency stop switch. | 10/18/2021 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.6 - Platforms | 2.6.6.3 Auxiliary Lighting (Re-Inspection) | No | No | Provide emergency overhead lighting in hoistway. | 7/18/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.7 - Capacity, Speed, and Travel | 2.7.2 | No | No | Provide capacity plates with operating instructions at each landing. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.10 - Operating Devices and Control Equipment | 2.10.1 | Yes | No | Provide call/send stations at each landing @ maximum height of 48" from the landing floor. | 10/18/2021 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.7 | No | No | Provide fused, lockable main line disconnect for lift power within sight of lift. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | 2.1 - Runways | 2.1.2.2 | No | No | Top landing gate and surrounding walls shall be a minimum of 42" tall from landing floor. | 9/30/2024 |
| ICC A117.1-2009 | 410.2 - Lift Entry | 410.2.1 | No | No | Provide low energy power operators at each landing door/gate. | 9/30/2024 |
| ASME A18.1-2005 : Lifts & Chairlifts | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | State Operating Certificate not available. Present site contact person has changed, however the Email address is correct. | 10/21/2025 |
| ASME A18.1-2005 : Lifts & Chairlifts | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Initial Violations have been corrected. Operating Certificate not available! | 10/21/2025 |