Inspection
Inspection Details
Equipment ID
22083
22083
Inspection Date
5/10/2018
5/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
1000
1000
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
16
16
External ID
6ad02464-9a40-4763-b78a-8d339537108b
6ad02464-9a40-4763-b78a-8d339537108b
Location
Hickey Elementary School
3111 CORA AVE, SAINT LOUIS, MO
3111 CORA AVE, SAINT LOUIS, MO
Owner
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
801 N 11TH ST, SAINT LOUIS, MO 63101-1015
Billing
Attn: Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601-0423
PO BOX 423, CHILLICOTHE, MO 64601-0423
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | x | x | Phase 1 fire recall shall be operational. - Elevator Red Tagged | 10/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone has intermittent communication repair as needed | 4/15/2024 | |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | x | Hoist cable has pulled strand replace within 90 days | 4/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Repair Battery lowering operation | 4/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Disconnect not provided with axillary contact. Car lowers when disconnect is pulled. Repair as needed | 4/15/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | OSV Trip speed test needs to be performed to complete the Cat 5 testing. | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Repair inoperative emergency phone. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Provide wiring to disconnect auxiliary switch for auxiliary battery lowering | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Adjust directional limit for proper runby |