Inspection
Inspection Details
Equipment ID
2140
2140
Inspection Date
10/13/2021
10/13/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
11"
11"
Governor Rope Pull
120/440
120/440
Door Closing Force
NA
NA
External ID
471b607c-b021-447a-ae00-755bb1a20ea6
471b607c-b021-447a-ae00-755bb1a20ea6
Location
Tower Village
5050 HIGHLAND AVE, SAINT LOUIS, MO
Phone: (314) 367-5050
5050 HIGHLAND AVE, SAINT LOUIS, MO
Phone: (314) 367-5050
Owner
Tower Village
5050 HIGHLAND AVE, SAINT LOUIS, MO 63113-1134
5050 HIGHLAND AVE, SAINT LOUIS, MO 63113-1134
Billing
Attn: Tower Village Apartments
5050 HIGHLAND AVE, SAINT LOUIS, MO 63113-1134
5050 HIGHLAND AVE, SAINT LOUIS, MO 63113-1134
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Repair Fire Service a. Car will not recall on phase 1 when car doors are open b. car doors will not come completely close and recall when turning phase 2 off in car | 2/8/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Fire Service Failed Will not return to recall level when keyed pff Phase II | 12/11/2018 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 206.5 | Yes | No | REplace hoist ropes within 30 days red rouge & reduced diameter | 2/28/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Repair fire service car will not respond on phase 1 with car doors open or phase 2 will not revert back to phase 1 with doors open | 2/28/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | Clean pit | 2/28/2020 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 108.1 | No | No | Replace cracked car floor tile at car entrance | 9/21/2022 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | Adjust car door operator excess door closing force | 9/21/2022 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Repair Machine Room Lights | 9/21/2022 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | Yes | No | Replace hoist ropes--red rouge--reduced diameter within 30 days | 10/13/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 9/21/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 9/21/2022 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 206 | Yes | Yes | Adjust governor--safeties in order to complete 5 year test | 10/13/2021 |