Inspection
Inspection Details
Equipment ID
17696
17696
Inspection Date
9/29/2021
9/29/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
0dda6fad-a034-40cf-923e-5dbd5b9fb030
0dda6fad-a034-40cf-923e-5dbd5b9fb030
Location
Delmar Loop Apartments
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Delmar Loop Apartments
c/o STL Apartments
1507 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: steve.bross@etrailer.com
c/o STL Apartments
1507 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: steve.bross@etrailer.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency lights shall work. | 1/2/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency bell and phone shall work. | 10/16/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe and convenient access to the elevator machine room. Wooden stairs leading to machine room are worn and unsafe. | 2/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit sump pump shall work. | 2/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove fluids from the pit. The pit shall be kept dry. | 2/28/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The doors stopped working during the inspection. All category 5 and annual inspection items have been completed with the exception of fire service. Fire service shall be tested as part of the category 5 annual inspection | 10/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car safety edge re-opening device does not work properly when car door is a foot from fully closing. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/4/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide code compliant machine room lighting. The illumination the machine room shall be not less than 10 foot-candles at the floor level. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Remove the bag covering the smoke detector in the machine room. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/29/2023 |