Inspection
Inspection Details
Equipment ID
12181
12181
Inspection Date
10/19/2021
10/19/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
475
475
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
80309edd-e985-4290-8033-aace34d50b20
80309edd-e985-4290-8033-aace34d50b20
Location
Walt Disney Elementary School
420 E California Ave, Marceline, MO
Phone: (660) 376-2166
420 E California Ave, Marceline, MO
Phone: (660) 376-2166
Owner
Marceline R-V School District
400 E SANTA FE AVE, MARCELINE, MO 64658-1568
400 E SANTA FE AVE, MARCELINE, MO 64658-1568
Billing
Attn: Marceline R-V School District
400 E SANTA FE AVE, MARCELINE, MO 64658-1568
400 E SANTA FE AVE, MARCELINE, MO 64658-1568
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Water not allowed to accumalate in pit. Need to repair or replace sump pump. | 8/14/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency elevator phone does not operate. | 8/14/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Need to remove standing water from elevator pit. | 10/5/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Emergency phone and bell do not operate. Elevator red tagged due to no emergency signaling | 12/9/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 11/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | 11/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Fire service log needed | 11/8/2021 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | The all missing & broken landing door pick-up roller's need replaced. Reference 8.6.4.13.1i) | 9/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The most current operating certificate shall be displayed in elevator machine room. | 9/26/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The Maintenance Control Program has not been initiated. School does not have a Maintenance Contract with an Elevator Company. | 9/26/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | New Phone system has been adapted and Elevator Emergency phone was not connected. | 9/13/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE WORKING PHONE (HAS POWER TO CONTROLLER) | 8/28/2026 |