Inspection
Inspection Details
Equipment ID
13424
13424
Inspection Date
10/20/2021
10/20/2021
Inspection Type
Alteration
Alteration
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
1cb70f84-2372-4d59-b7e6-cdfb0a0f85b3
1cb70f84-2372-4d59-b7e6-cdfb0a0f85b3
Location
McCormack House
3915 Olive St, St. Louis, MO
Phone: (314) 531-8844
3915 Olive St, St. Louis, MO
Phone: (314) 531-8844
Owner
House at Westminster
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
Billing
Attn: House at Westminister
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 7/24/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency battery lowering device does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | One bulb in emergency light does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | When unit was put on ring, excessive fluid leakage from top Vic fitting (below valve) or bottom of valve. Repair as needed. | 7/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be properly displayed in machine room. | 7/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace bad light bulb in emergency light fixture. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communications, no one answered. Reinspect required. | 8/11/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering system shall work. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Need to replace bad light bulb in emergency light fixture. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communication. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/15/2024 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | Yes | No | Car failed 15 minute stand test, technician determined that it is leaking back through the valve. | 3/27/2025 |