Inspection
Inspection Details
Equipment ID
5661
5661
Inspection Date
10/22/2021
10/22/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
16
16
External ID
1c388fb6-0a64-493e-ad3e-6dba5654e981
1c388fb6-0a64-493e-ad3e-6dba5654e981
Location
OLTUC Bldg
1139 Olive St, St. Louis, MO
Phone: (314) 486-5623
1139 Olive St, St. Louis, MO
Phone: (314) 486-5623
Owner
Attn: Front Page Lofts, LLC
Front Page Lofts, LLC
300 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 726-0000
Email: mpmasiel@screamingeagledevelopment.com
Front Page Lofts, LLC
300 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 726-0000
Email: mpmasiel@screamingeagledevelopment.com
Billing
Attn: Front Page Lofts, LLC
Front Page Lofts, LLC
7777 Bonhomme Ave, Ste 210, St. Louis, MO 63105
Phone: (314) 920-9051
Email: mpmasiel@screamingeagledevelopment.com
Front Page Lofts, LLC
7777 Bonhomme Ave, Ste 210, St. Louis, MO 63105
Phone: (314) 920-9051
Email: mpmasiel@screamingeagledevelopment.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator machine room cannot be used for storage. Remove the items (old AC units) being stored in the machine room to provide proper room for maintenance to be performed. | 7/10/2018 |
| conversion | conversion | n/a | No | No | The fire extinguisher in the machine room needs to be serviced, the last annual service tag indicates it was serviced in 2016. | 7/10/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not work | 3/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | Yes | Suspension ropes are showing rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes. | 5/14/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | Yes | The pullout is higher than the pull through of the governor. The safetiies releasing carrier does not pull out when the jaw is fully set. | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Replace the broken springs located on the suspension rope shackles and tension the ropes | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The anti-rotation cable on the car side suspension shackles is frayed and coming apart. Replace the anti-rotation cable. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide a governor rope data tag | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete. Need to test pullout/pull through, set the safeties with a full load, fire service, 110 back up power, counter weight buffer, and emergency phone | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. | |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.7.3.16 | Yes | No | 8.7.2.19 - Provide a Governor rope data tag (2.18.5.3) |