Inspection
Inspection Details
Equipment ID
6623
6623
Inspection Date
8/6/2021
8/6/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
710
710
Slide
Governor Rope Pull
Door Closing Force
18F/18R
18F/18R
External ID
89d7690d-64d8-44f5-9a4d-22114284f047
89d7690d-64d8-44f5-9a4d-22114284f047
Location
Ross
50 Hampton Village Plz, St. Louis, MO
Phone: (314) 994-2345
50 Hampton Village Plz, St. Louis, MO
Phone: (314) 994-2345
Owner
Attn: Marnie Clark
The Desco Group
25 N Brentwood Blvd, St. Louis, MO 63105
Phone: (314) 994-4075
Email: Nazira.Harooni@ros.com
The Desco Group
25 N Brentwood Blvd, St. Louis, MO 63105
Phone: (314) 994-4075
Email: Nazira.Harooni@ros.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean elevator pit | 5/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. (Repeat Violation) | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | The light switch in the machine room shall be a toggle switch. The automatic switch shall be removed. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and dry. Remove water and trash from the pit. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 3.27 The in car emergency telephone shall be operational. (Repeat Violation) | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | The light switch in the machine room shall be a toggle switch. The automatic switch shall be removed. | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | 8.6.4.7 The pit shall be kept clean and dry. Remove water and trash from the pit. | 3/5/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate. | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.1.6.5 Fire Extinguishers | No | No | No fire extinguisher located in machine room. |