Inspection
Inspection Details
Equipment ID
15005
15005
Inspection Date
10/4/2021
10/4/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
23F/23R
23F/23R
External ID
5eb2ac65-7ae3-4e76-a9e1-07c4dc7aeda4
5eb2ac65-7ae3-4e76-a9e1-07c4dc7aeda4
Location
Crider Health Center
1032 Crosswinds Ct, Wentzville, MO
Phone: (636) 332-6000
1032 Crosswinds Ct, Wentzville, MO
Phone: (636) 332-6000
Owner
Attn: Kevin O’Laughlin
Crider Center for Mental Health
1032 Crosswinds Ct, Wentzville, MO 63385
Phone: (636) 332-6000
Email: kolaughlin@compasshn.org
Crider Center for Mental Health
1032 Crosswinds Ct, Wentzville, MO 63385
Phone: (636) 332-6000
Email: kolaughlin@compasshn.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Sump pump hole shall have a code compliant cover. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be functional. | 1/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | All 3 units at location are due for category 5 testing of the overspeed valve in 2024. | 11/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering shall work. Repair or replace. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Jack packings are leaking. Repack/repair as needed. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess oil. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | The car operating panel fire service access door is damaged. Repair or replace as needed. | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery Lowering shall work | 12/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Jack packings are leaking | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be lept clean/ Remove excess oil | 12/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | The car operating panel is damaged. Repair or Replace | 12/1/2025 |