Inspection
Inspection Details
Equipment ID
17238
17238
Inspection Date
10/6/2021
10/6/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
819c13fa-4b62-44a1-b5f9-43e162169a9b
819c13fa-4b62-44a1-b5f9-43e162169a9b
Location
Cheesecake Factory Restaurants Inc
1062 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 721-3570
1062 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 721-3570
Owner
Attn: Westfield Properties
Westfield Properties
1062 Saint Louis Galleria, Richmond Heights, MO 63117
Phone: (000) 000-0000
Westfield Properties
1062 Saint Louis Galleria, Richmond Heights, MO 63117
Phone: (000) 000-0000
Billing
Attn: Cheesecake Factory Restaurant Inc
Cheesecake Factory Restaurant Inc
1062 Saint Louis Galleria, Richmond Heights, MO 63117
Phone: (000) 000-0000
Cheesecake Factory Restaurant Inc
1062 Saint Louis Galleria, Richmond Heights, MO 63117
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 2/10/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 2/10/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Perform monthly fire service test & document on log in machine room | 2/10/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall remain operative when 110v source is removed. | 10/6/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 2/10/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 3/17/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Machine room lighting shall be a minimum of 10 foot-candles at the floor. | 3/17/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Cab lighting shall be guarded. | 3/17/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. Remove excess debris, including several cigarette butts. | 4/7/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lights shall work. | 4/9/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the machine room. | 4/9/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | Yes | No | Elevator car floor is damaged and not maintained in a safe condition. | 9/2/2026 |