Inspection
Inspection Details
Equipment ID
5895
5895
Inspection Date
10/28/2021
10/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Thomas LeMasters
Thomas LeMasters
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
0302046a-3af9-4452-902b-e0c9f923059c
0302046a-3af9-4452-902b-e0c9f923059c
Location
Greene County Library
397 E Central St, Springfield, MO
Phone: (000) 000-0000
397 E Central St, Springfield, MO
Phone: (000) 000-0000
Owner
Attn: Greene County Library
Greene County Library-Springfield
4653 S CAMPBELL AVE, SPRINGFIELD, MO 65810
Phone: (417) 616-0568
Email: lelandb@thelibrary.org
Greene County Library-Springfield
4653 S CAMPBELL AVE, SPRINGFIELD, MO 65810
Phone: (417) 616-0568
Email: lelandb@thelibrary.org
Billing
Attn: Green County Library-Springfield
4653 S CAMPBELL AVE, SPRINGFIELD, MO 65810
Phone: (417) 616-0568
Email: lelandb@thelibrary.org
4653 S CAMPBELL AVE, SPRINGFIELD, MO 65810
Phone: (417) 616-0568
Email: lelandb@thelibrary.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | repair greenfield connections on top of elevator | 9/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | alarm bell and telephone do not function | 9/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | door restrictor does not work | 9/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | Yes | No | 3.19.4.7.5 overspeed valve needs to be tested | 9/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | Dpor pressure exceeds 30 pounds | 9/8/2020 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Updated Certificate of operation | 11/19/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No Records | 11/19/2020 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 8.11.3.1.2(b) | No | No | Repair Door closer | 11/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide proper pit containers for jack oil collection | 12/18/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Has speed valve (No Tag) | 12/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 2.22 | Yes | No | Buffers to be mounted properly | 6/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide operational telephone | 12/18/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide operational telephone | 12/18/2025 |