Inspection
Inspection Details
Equipment ID
10448
10448
Inspection Date
10/4/2021
10/4/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
6f9f0fb5-4d24-4147-9a94-5a0b1c26bf8b
6f9f0fb5-4d24-4147-9a94-5a0b1c26bf8b
Location
Washington Place
132 W WASHINGTON AVE, KIRKWOOD, MO
Phone: (314) 965-8600
132 W WASHINGTON AVE, KIRKWOOD, MO
Phone: (314) 965-8600
Owner
Attn: David Bridges
Landmark Real Estate Group
206 W ARGONNE DR STE 201, SAINT LOUIS, MO 63122
Phone: (314) 965-9110
Email: dave@landmarkreg.com
Landmark Real Estate Group
206 W ARGONNE DR STE 201, SAINT LOUIS, MO 63122
Phone: (314) 965-9110
Email: dave@landmarkreg.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The elevator pit shall be kept clean and dry. | 3/19/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit has several inches on water in it. The pit shall be kept dry. | 2/28/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency lighting shall be operational. | 11/23/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/2/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/28/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | OSV testing incomplete. Existing OSV cold not be adjusted for proper setting speed due to rust/damage from previous water intrusion in pit. Repair/replace as needed for proper operations. | 4/16/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Low pressure switch to be tested. | 4/16/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/2/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 4/16/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall work with loss of main 120v power. | 4/16/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Fire service shall be tested and documented monthly. | 4/16/2026 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Hoistway shall be enclosed throughout its height with fire-resistive enclosure. There are large voids under the 2nd floor (3rd landing) sill that extend several feet into the adjoining ceiling. Fill with appropriate fire resistant material. Also, exposed wood under 1st floor (2nd landing) sill that shall be covered with fire resistant coating. | 3/2/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak that is still present. | 3/2/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Jack head drain tubes shall be routed to measurable containers in the pit, currently ran back to tank with no way to account for lost oil. Containers not to exceed 5gal per jack. | 3/2/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not work. | 5/1/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not work. | 5/1/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Yes | No | Pit shall be kept clean and dry | 5/1/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | Yes | No | Jack head drain tubes shall be routed to mesurable containers in the pit, currently ran back to tank with no way to account for lost oil. | 5/1/2026 |