Inspection
Inspection Details
Equipment ID
888
888
Inspection Date
11/1/2021
11/1/2021
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
Slide
1 3/4"
1 3/4"
Governor Rope Pull
50 lbs. / 400 lbs.
50 lbs. / 400 lbs.
Door Closing Force
18
18
External ID
a1e38bde-c8ac-4e13-bd9e-fab4c0e25986
a1e38bde-c8ac-4e13-bd9e-fab4c0e25986
Location
Senate Garage
201 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 522-2514
201 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 522-2514
Owner
Attn: INTERAGENCY
State of MO- Capitol Bldg- INTERAGENCY
301 W High St, Rm 590, Jefferson City, MO 65101
Phone: (000) 000-0000
Email: Brad.berendzen@oa.mo.gov
State of MO- Capitol Bldg- INTERAGENCY
301 W High St, Rm 590, Jefferson City, MO 65101
Phone: (000) 000-0000
Email: Brad.berendzen@oa.mo.gov
Billing
Attn: INTERAGENCY
OA-FMDC-INTERAGENCY
301 W High St, HST Rm 730, Jefferson City, MO 65102
Phone: (000) 000-0000
OA-FMDC-INTERAGENCY
301 W High St, HST Rm 730, Jefferson City, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Needs a pit light. | 1/25/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | Needs a pit ladder. | 1/25/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Provide an HVAC system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 | 9/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide an MCP in machine room to log maintenance, repairs, and inspections. | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide guarding for lighting above drive machine in machine room. 2.7.5.1 | 9/20/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Provide a GFCI outlet in machine room. | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Main line disconnect not labeled with feed source. 2.26.4.1 | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Car light disconnect not labeled with feed source. 2.26.4.1 | 9/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 9/20/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a cover for sump pump in machine room/pit. | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Provide and HVAV system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Provide feed source for main line disconnect. | 9/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Provide feed source for cab light disconnect. | 8/20/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Provide a GFCI outlet in machine room. | 8/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten ropes. | 12/17/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide guarding for lighting above machine. | 8/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Secure pit ladder. | 8/20/2026 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | Yes | No | Adjust governor rope tension device in pit. | 12/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Provide an HVAC system in machine room to keep equipment within safe operating ranges. | 8/20/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Provide a GFCI service outlet in machine room. | 8/20/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide guarding for lighting above drive machine in machine room. 2.7.5.1 | 8/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a cover for sump pump in machine room/pit. | 8/20/2026 |