Inspection
Inspection Details
Equipment ID
19791
19791
Inspection Date
11/2/2021
11/2/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
5eed7f58-0405-40fc-a9aa-a68c10655444
5eed7f58-0405-40fc-a9aa-a68c10655444
Location
The Parkdale
7518 Parkdale Ave, Clayton, MO
Phone: (314) 726-3320
7518 Parkdale Ave, Clayton, MO
Phone: (314) 726-3320
Owner
Attn: Efthim Realtors Co
Efthim Realtors Co
4177 Crescent Dr, Ste A, St. Louis, MO 63129
Phone: (314) 845-0377
Email: efthimmgmt@sbcglobal.net
Efthim Realtors Co
4177 Crescent Dr, Ste A, St. Louis, MO 63129
Phone: (314) 845-0377
Email: efthimmgmt@sbcglobal.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in not sealed and must have a cat 5 weight test performed | 3/16/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A written Maintenance Control Program shall be kept on site | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm inoperable on battery, emergency lights are also not working. Re-inspection required | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired. Have serviced or replaced | 11/17/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed and must have Cat 5 full load test performed. Re-inspection required | 3/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room | 11/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher. Except in jurisdictions enforcing NBCC, class "ABC" fire extinguishers shall be provided in elevator electrical machinery and control spaces, walk-in machinery and control rooms for escalators and moving walks, and shall be located convenient to access door. Extinguisher has no date of when it was serviced. | 11/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A written maintenance control program shall be kept on site. | 11/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | alarm inoperable on battery | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | emergency lights are not working | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Except in jurisdictions enforcing NBCC, Class ABC fire extinguishers shall be provided in elevator electrical machinery and control spaces, walk-in machinery and control rooms for escalators and moving walks, and shall be located convenient to the access door. Extinguisher has no date of when it was serviced. | 11/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 11/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Except in jurisdictions enforcing NBCC, Class ABC fire extinguishers shall be provided in elevator electrical machinery and control spaces, walk-in machinery and control rooms for escalators and moving walks, and shall be located convenient to the access door. Extinguisher has no date of when it was serviced. | 11/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 11/30/2023 |