Inspection
Inspection Details
Equipment ID
25510
25510
Inspection Date
10/11/2021
10/11/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
626d947f-dbe0-4803-8ed9-5d50e57e3007
626d947f-dbe0-4803-8ed9-5d50e57e3007
Location
Avalon Park
1101 Cottleville Trails Dr, Cottleville, MO
Phone: (000) 000-0000
Email: esb@benhurconstruction.com
1101 Cottleville Trails Dr, Cottleville, MO
Phone: (000) 000-0000
Email: esb@benhurconstruction.com
Owner
Attn: Meghan Schmitz
Avalon Park Senior Living
11001 Cottleville Trails Dr, Cottleville, MO 63304
Phone: (636) 251-4400
Email: meghan.schmitz@avalonparksl.com
Avalon Park Senior Living
11001 Cottleville Trails Dr, Cottleville, MO 63304
Phone: (636) 251-4400
Email: meghan.schmitz@avalonparksl.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | x | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 100 lx (10fc). | 9/2/2021 | |
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.10.2.2.2(l) | x | An ABC fire extinguisher with a current test tag shall be mounted convenient to the fourth floor hall door. | 9/2/2021 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. Note: The telephone line monitor shall be tested once the phone line is installed and operational. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 8.10.2.2.2(o) | x | A unique identification (alphabetic, numeric, or alphanumeric) with a minimum of 2 inches in height and of contrasting color to its background shall be applied on both door jambs of every elevator entrance at the designated level, alternate level, and level where means necessary for tests is provided and shall be located immediately below the floor designations. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 8.10.2.2.2(o) | x | A unique identification (alphabetic, numeric, or alphanumeric) with a minimum of 2 inches in height and of contrasting color to its background shall be applied to the buffers or pit channels in the pit, visible from the pit access door landing. | 9/2/2021 | |
A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.10.2.2.1(o) | x | Floor designations with raised and braille characters shall be installed at all floors on every door jamb with the center line at 60" and shall be a minimum of 2" in height and of contrasting color to its background. | 9/2/2021 | |
A17.1-2016 : Elevators | 1.4 - Sills and car floor | 8.10.2.2.1(d) | x | The flooring on the landings and on the car shall be installed. | 9/2/2021 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The lobby to car phone shall be operational. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | x | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/2/2021 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | The emergency/standby power shall be tested with 125% of rated load. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.10.2.2.2(m) | x | All missing wireway covers shall be installed. | 9/2/2021 | |
A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | x | Feeder locations for the main and lighting branch circuits shall be marked in the elevator controller. | 9/2/2021 | |
A17.1-2016 : Elevators | 3.20 - Governor rope | 8.10.2.2.3(z) | x | The governor rope shall be tagged as specified by A17.1 | 9/2/2021 | |
A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.10.2.2.3(cc) | x | The suspension ropes shall be tagged as specified by A17.1 | 9/2/2021 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.10.2.2.2(m) | x | Where the elevator is located on its enclosure configured such that the application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator. | 9/2/2021 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | x | A selector switch and a visual indicator is required for emergency power. | 10/11/2021 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | x | The sump pump shall have a discharge capacity of 6000 GPH. | 10/11/2021 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | The sump pump shall have a discharge capacity of 6000 GPH. | 10/21/2021 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Fire service testing is not being documented monthly. | 7/17/2024 |